Cyber Power Datacenter UPS Systems HSTP3T30KEBC

42,521,000.00 MMK 42521000.0 MMK 42,521,000.00 MMK

42,521,000.00 MMK

  • Phase
  • Form Factor
  • UPS Topology
  • Energy Saving Technology
  • Normal Mode Efficiency
  • Battery Mode Efficiency
  • Features
  • Parallel Expansion
  • Nominal Input Voltage ( Vac )
  • Input Voltage Range ( Vac )
  • Configurable Voltage Range
  • Input Frequency
  • Input frequency range
  • Rated Input Current ( A )
  • THD
  • Input Power Factor
  • Input Connector Type
  • Capacity
  • On Battery Waveform
  • Output Voltage/ Frequency Setting
  • Rated Output Voltage
  • Output Voltage Tolerance
  • Output Frequency ( Hz )
  • ECO Mode Voltage Tolerance
  • overload protection
  • Crest Factor
  • Harmonic Distortion
  • Internal Bypass
  • Outlet Type:
  • Runtime
  • Recharge Power
  • Battery Type
  • Battery Quantity (Each RBP)
  • Battery Voltage (Each RBP)
  • Single Battery Capacity
  • LCD Information Display
  • LCD Setting & Control
  • Serial Port
  • Audible Alarms
  • Power Management Software
  • Enclosure Construction
  • Color
  • Ingress Protection
  • Warranty

This combination does not exist.

Phase: Three Phase
Form Factor: Tower
UPS Topology: Online Double Conversion
Energy Saving Technology: Online ECO Mode Efficiency > 98%
Normal Mode Efficiency: 0.95%
Battery Mode Efficiency: 0.95%
Features: Active PFC Compatibility, Dual Power Inputs, Generator Compatibility, Maintenance Bypass, EMI/RFI Filtration, LCD Panel, LED Indicators, Emergency Power Off (EPO) Port
Parallel Expansion: 4 (Max. Units)
Nominal Input Voltage ( Vac ) : Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac
Input Voltage Range ( Vac ): Line to Neutral (L-N): 132 ~ 276 Vac Line to Line (L-L): 228 ~ 478 Vac
Configurable Voltage Range: Line to Neutral (L-N): 220 ~ 250 Vac Line to Line (L-L): 380 ~ 435 Vac
Input Frequency: 50 ± 3/ 60 ± 3(Hz)
Input frequency range: 40 ~ 70 (Hz)
Rated Input Current ( A ) : 42
THD: <3% (Full Linear Load)
Input Power Factor: 0.99
Input Connector Type: Hardwire Terminal Block
Capacity: 30000 (VA)/27000 (Watts)
On Battery Waveform: Pure Sine Wave
Output Voltage/ Frequency Setting: Configurable/Configurable
Rated Output Voltage: Line to Neutral (L-N):220, 230, 240 Vac, Line to Line (L-L):380, 400, 415 Vac
Output Voltage Tolerance: 1.5 %
Output Frequency ( Hz ) : 50 ± 0.1/ 60 ± 0.1
ECO Mode Voltage Tolerance: ± 10 %
overload protection: Internal Current Limiting, Circuit Breaker, Fuse, 105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately(Line Mode),105~110% Load for 60 min, 110~125% Load for 10 min, 125~150% Load for 1 min, >150% Load Immediately(Battery Mode), 125~130% Load for 10 min, 130~150% Load for 1 min, 150~400% Load for 1 sec, >400% Load Immediately(Bypass Mode)
Crest Factor: 0.125694
Harmonic Distortion: THD<1%(Linear Load),THD<5.5%(Non-linear Load)
Internal Bypass: Automatic Bypass, Manual Bypass
Outlet Type:: Hardwire Terminal Block x 1
Runtime: 9 min(Half Load),1 min(Full Load)
Recharge Power: Default 10 % (Selectable from 1~20% x UPS Capacity)
Battery Type: VRLA
Battery Quantity (Each RBP): 40 pcs
Battery Voltage (Each RBP): 240 V
Single Battery Capacity: 12 V 12 AH
LCD Information Display : : Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log
LCD Setting & Control : Mode Setting, Input & Output, Battery Setting, Communication, Event & Log, Security Setting, Language
Serial Port: RS232 x 1 + RS485 x 1 + Dry Contact x1
Audible Alarms : Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery
Power Management Software: PowerPanel Business (Recommended)
Enclosure Construction: Metal
Color: Black
Ingress Protection: IP20
Warranty: 1 Year Battery , 2 Years Parts , 3 Years Service

Terms and Conditions