Phase:
Single Phase
|
Form Factor:
Tower
|
Energy Saving Technology:
Online ECO Mode Efficiency > 96%
|
UPS Topology:
Online Double Conversion
|
Features:
Active PFC Compatibility, Generator Compatibility, Maintenance Bypass, Start On Battery, Smart Battery Management (SBM), EMI/RFI Filtration, LCD Panel, Emergency Power Off (EPO) Port
|
Parallel Expansion:
4 (Max. Units)
|
Nominal Input Voltage ( Vac ) :
230 Vac
|
Input Voltage Range:
110 ~ 276(Vac)
|
Adjustable Voltage Range:
0~80% Load for 110 ~ 276 Vac/ 0~100% Load for 176 ~ 276 Vac
|
Input Frequency:
50 ± 5/ 60 ± 6(Hz)
|
Input Frequency Detection:
Auto-sensing
|
Rated Input Current ( A ) :
27.3
|
Input Power Factor:
0.99
|
Input Connector Type:
Hardwire Terminal Block
|
Capacity:
6000 VA/5400 Watts
|
On Battery Waveform:
Pure Sine Wave
|
On Battery Voltage(s):
208 ± 1%/ 220 ± 1%/ 230 ± 1%/ 240 ± 1%(Vac)
|
Output Voltage/ Frequency Setting:
Configurable/Configurable
|
On Battery Frequency:
50 ± 0.1%/ 60 ± 0.1%(Hz)
|
ECO Mode Voltage Tolerance:
± 10 %
|
overload protection:
Internal Current Limiting, Circuit Breaker, Fuse, 110~120% Load for 1 min, >120% Load Immediately(Line Mode),110~120% Load for 10 sec, >120% Load Immediately(Battery Mode),>130% Load Immediately(Bypass Mode)
|
Crest Factor:
0.125694
|
Harmonic Distortion:
THD<2%(Linear Load),THD<5%(Non-linear Load)
|
Internal Bypass:
Automatic Bypass, Manual Bypass
|
Outlet(s) :
Total : 1
|
Outlet Type::
Hardwire Terminal Block x 1
|
Typical Transfer Time ( ms ):
0
|
Runtime:
18 min(Half Load),7 min(Full Load)
|
Typical Recharge Time:
7 Hours
|
maximum charge current:
1 A
|
Battery Type:
Sealed Lead-acid
|
Compatible Extended Battery Module:
BPSE240V47A
|
Max. EBM Quantity :
15 pcs
|
Surge Suppression ( Joules ):
445
|
LCD Information Display :
: Operation Type, Power Status, Battery Status, Load Status, Fault & Warning, Other Information, Event & Log
|
LCD Setting & Control :
Mode Setting, Alarm Setting, Input & Output, Battery Setting, Fault & Warning, Communication, Event & Log, Security Setting
|
LED Indicator:
Line Mode, Battery Mode, Bypass Mode, UPS Fault
|
Audible Alarms :
Battery Mode, Low Battery, Overload, Overcharge, Overheat, UPS Fault, Replace Battery
|
Management Cable:
USB Cable x1(pcs)
|
Power Management Software:
PowerPanel Business (Recommended)
|
Enclosure Construction:
Metal
|
Color:
Black
|
Warranty:
1 Year Battery , 2 Years Parts , 3 Years Service
|